Call UsCall Us : +919910605527
Electrical Rubber Mat

Electrical Rubber Mat

550 INR/Meter

Product Details:

X

Electrical Rubber Mat Price And Quantity

  • 10 Meter
  • 550 INR/Meter

Electrical Rubber Mat Trade Information

  • 1000 Meter Per Week
  • 1 Week

Product Description

Backed by a team of experts, we have been a prestigious manufacturer of Electrical Rubber Mat in the market. It is made in compliance with the IS:15652-2006 standards using best in grade raw material and machinery. Electrical Rubber Mat is used for electrical purposes for the safety of electricians by providing the insulation against electricity and preventing the electric shocks.
 

Specification : 

Product Code

Class

Recommended Thickness

Max use/Working Voltage

AC Proof Voltage

Di-electric strength (withstand Voltage)

Approx weight per Sq Mtr

IEC001

0

3.0 mm

1.0KV

5.0 KV

6.0 kgs

5.0 Kgs

IEC002

1

4.0 mm

7.5KV

10.0kv

20.0 KV

7.0 Kgs

IEC003

2

5.0 mm

17.0 KV

20.0 KV

30.0 KV

8.0 Kgs

IEC003

4

6.0 mm

26.5 KV

30.0 KV

40.0 KV

9.0 Kgs

ASTM CD (Custom)

-

Upto 25.0mm

Upto 36.0KV

Upto 40.0 KV

Upto 50.0 KV

-

Other Details :

  • Size : As per IS standard width is normally 1Mtr x 2Mtr., 1.2Mtr. x 2Mtr. And long length as per customer requirements.
  • Marking & Packaging : AS Per IS: 15652 (clausse 9)
  • Surface : Upper surface of the mat is having small anti-skid aberration (rough surface without edges) to avoid slippery effects and lower surface is plain.

Salient Features of Electrical Insulating Mats :

  • Tests and specification of insulating mats meets IS: 15652/2006 and tested by ERDA, BIS and self.
  • For both ac and current applications.
  • Insulating mats having low temperature resistance.
  • Insulating mats have acid alkalis transformer oil and diesel oil resistance.
  • Excellent flame retardant
  • Excellent ageing properties
  • Water and moisture proof.

Salient Features : 

  • High Voltage panels.
  • Power transmission rooms.
  • Near buss- bras.
  • Near control panels etc.
  • High voltage equipment.
  • AC plant rooms.
  • Workshop
  • Indoor or outdoor portable protection element
  • Lift machine rooms
  • Electrical switch gears

TECHNICAL SPECIFICATIONS AS PER IS: 15652/2006  

S.No.

Characteristics

Standard

Values

1.

Minimum Thickness

2.0 mm

2.5 mm

2.

Workmanship and finish

The mat shall be free on both surface from pinholes, cracks, cuts blisters, conduction embedded foreign matter, creases, pinch mark, voids & prominent ripples

The mat shall be free on both surface from pinholes, cracks, cuts, blisters, conductive embedded foreign matter, creases pinch mark voids& prominent ripples

3.

Tensile strength (N/mm2)

15 Min

15 Min

4.

Elongation at break (%)

250 min

250 min

5.

Insulation resistance with water at 5000v

1,00,000M min.

1,00,000 M min.

6.

Leakage current at 11 KV

10mA, max.

10mA, max.

7.

Dielectric strength

30kv ac (rms), min.

45kv ac (rms), min.

8.

Ac proof voltage

Mat shall withstand 10kV ac (rms) for 3 minutes without failure

Mat shall withstand 22kV ac (rms) for 3 minutes without failure

9.

Low temperature resistance at- 10oC

Mat shall not show any visible break or crack

Mat shall not show any visible break or crack

10.

Flame retardant

Fire should extinguish within 5 second after removal of blue flame

Fire should extinguish within 5 second after removal of blue flame

11.

Effect to acid, alkali transformer oil, diesel retention of tensile strength (N/mm2) & elongation

80% min.

80% min.

12.

Ageing properties at 70+1oC for 168hrs. retention of tensile (N/mm2) & elongation(%)

75% min.

75% min.

Specification

Thickness Range

2 to 10mm

Usage/Application

Electrical Insulation

Pattern

Checkered

Brand

Siddhi

Working Temperature

-10 to +120 deg C

Color

Black

Dielectric Strength

30 kV ac (rms) to 45 kV ac (rms)

Elongation

Min 250%

Material

Rubber

Size/Dimension

1 x 2 m,1.2 x 2 m

Tensile Strength

Min 15 N/mm2

 

Enter Buying Requirement Details
Email Id
Mobile number

Other Products in 'Rubber Mat' category